Measuring Range: -40 a +105°C
Degree of protection: IP40 (front)
2 outputs with unipolar relay in deviation
Power supply: 230 V a.c. ± 10 %
Contact capacity: 240 Vac , 16 A (resistive); 4 A (inductive),
Self-consumption: 3 W
Control: ON/OFF or PID – Output ON or OFF depending on the incoming
temperature, set point and hysteresis values set. The hysteresis is the value of
the deviation from the set point that determines the reactivation of the output.
Alarm management: output 2
Proportional control and integrative proportional
Minimum or maximum set point limits
Operating temperature: -10 a +50°C
Dimensions: L 71 x H 98 x W 61